Arc Flash Platform — Estudos Elétricos
REMOTE · ARC-FLASH-PLATFORM.ONRENDER.COM · SCANNED OCT 3
Cálculos de engenharia elétrica pela norma brasileira (NBR), validados, com citação normativa.
Available components
How this component scores in each security and reliability category. Every signal is checked automatically against the live server, and we only credit what we can confirm. How we score → Why this is hard to score →
Endpoint Security74
- The endpoint's TLS certificate is valid, in date, and uses a strong key. View diagnostics → Pass
- No authorisation is required to call this server. Every tool declares its destructiveHint and none is destructive, so open access doesn't expose one. See how to fix → View diagnostics → Partial
- HTTPS is enforced; there's no plaintext access path. View diagnostics → Pass
- HSTS check failed: the Strict-Transport-Security header is absent. See how to fix → View diagnostics → Fail
- DNSSEC check failed: this domain isn't protected by DNSSEC. See how to fix → View diagnostics → Fail
Transport & Reachability100
- Verified streamable-http transport via a live MCP handshake. View diagnostics → Pass
Schema Quality & AI Usability56
- AI-judged instruction clarity (good).Pass
- Context-footprint check failed: tool/resource definitions use about 6513 tokens (~310/item across 21 items; 21 tools + 0 resources), over budget; trim descriptions and params. See how to fix → Fail
- Usage-examples check failed: none of the tools include examples. See how to fix → Fail
Stability & Change Management100
- No destabilizing schema changes in the last 30 days.Pass
Tool Coverage67
- 100% of tools have a non-trivial description (not blank, and not just the tool's name).Pass
- 0% of tool parameters carry a description.Fail
Tool Safety100
- No prompt-injection markers were found in the server instructions, tool names or descriptions we captured.Pass
- We read all 21 captured tool definition(s), and no name or description among them implies an irreversible operation.Pass
- An AI judge read all 21 captured unit(s) of tool text and found none that tries to manipulate the model reading it.Pass
Capabilities100
- Implements a supported MCP spec version (2025-11-25); the latest is 2026-07-28.Pass
How do I install the Arc Flash Platform — Estudos Elétricos MCP server?
Arc Flash Platform — Estudos Elétricos is a hosted endpoint at https://arc-flash-platform.onrender.com/mcp, so there is nothing to install locally. Ready-made configuration for Claude, Cursor, VS Code, Codex and 5 more is on this page, copied from each client's own documentation.
remote · arc-flash-platform.onrender.com
claude mcp add --transport http alessandropeng-arc-flash-platform 'https://arc-flash-platform.onrender.com/mcp'
{
"mcpServers": {
"alessandropeng-arc-flash-platform": {
"url": "https://arc-flash-platform.onrender.com/mcp"
}
}
} {
"servers": {
"alessandropeng-arc-flash-platform": {
"type": "http",
"url": "https://arc-flash-platform.onrender.com/mcp"
}
}
} [mcp_servers.alessandropeng-arc-flash-platform] url = "https://arc-flash-platform.onrender.com/mcp"
{
"$schema": "https://opencode.ai/config.json",
"mcp": {
"alessandropeng-arc-flash-platform": {
"type": "remote",
"url": "https://arc-flash-platform.onrender.com/mcp",
"enabled": true
}
}
} openclaw mcp add alessandropeng-arc-flash-platform --url 'https://arc-flash-platform.onrender.com/mcp' --transport streamable-http
mcp_servers:
alessandropeng-arc-flash-platform:
url: "https://arc-flash-platform.onrender.com/mcp" {
"McpServers": {
"alessandropeng-arc-flash-platform": {
"Transport": "http",
"Url": "https://arc-flash-platform.onrender.com/mcp"
}
}
} assistant mcp add alessandropeng-arc-flash-platform -t streamable-http -u 'https://arc-flash-platform.onrender.com/mcp'
{
"mcpServers": {
"alessandropeng-arc-flash-platform": {
"type": "http",
"url": "https://arc-flash-platform.onrender.com/mcp"
}
}
} The mcpServers block is a cross-client convention. Remote transports vary, so check your client's docs.
Every change we have recorded for this component, newest first. Security-relevant changes are always shown. ▲ marks a change for the better, ▼ a change for the worse; unmarked changes are neutral.
- 29 Sept 26 0
- Endpoint reachability: not serving MCP → reachable ▲ functional
- 28 Sept 26 +56
- We updated how we score, so this day's move reflects our rubric, not a change to the server See what changed → functional
- 27 Sept 26 −49
- Endpoint reachability: reachable → not serving MCP ▼ security
- Stability: pass → unverified ▼ security
- Tool safety: pass → unverified ▼ security
- Transport: pass → fail ▼ security
- Authorization: Authorisation not fully verified: no authorisation is required to connect, but we couldn't read the whole tool list to see what that exposes. security
- Capabilities: pass → unverified ▼ functional
- Tool coverage: 100 → unverified ▼ functional
- First check of Schema quality: unverified functional
- 25 Sept 26 0
- We updated how we score, so this day's move reflects our rubric, not a change to the server See what changed → functional
- 9 Sept 26 0
- Server version: 1.29.0 → 1.30.0 functional
- 26 Aug 26 0
- We updated how we score, so this day's move reflects our rubric, not a change to the server See what changed → functional
- 25 Aug 26 0
- Stability: 0.97 → pass security
- 17 Aug 26 0
- Schema quality: 277 → 310 ▼ functional
- Server version: 1.28.1 → 1.29.0 functional
- New tool “montar_rede” functional
Diagnostic detail from the automated scan of this channel: what the scanner observed at each step, so you can see exactly where a check passed or failed. It is informational only and never changes the trust score.
Captured 3 Oct 2026 · Probed https://arc-flash-platform.onrender.com/mcp
TLS valid
Negotiated TLS 1.3 with TLS_AES_128_GCM_SHA256 .
| Subject | Issuer | Valid from | Valid until | Key | Signature | Serial |
|---|---|---|---|---|---|---|
| CN=onrender.com | CN=WE1,O=Google Trust Services,C=US | 21 Sept 2026 | 20 Dec 2026 | ECDSA 256 | ECDSA-SHA256 | 6eb1e3fe7d0631ea1337bfa4a321c137 |
| SANs: onrender.com, *.onrender.com | ||||||
| CN=WE1,O=Google Trust Services,C=US (CA) | CN=GTS Root R4,O=Google Trust Services LLC,C=US | 13 Dec 2023 | 20 Feb 2029 | ECDSA 256 | ECDSA-SHA384 | 7ff31977972c224a76155d13b6d685e3 |
| CN=GTS Root R4,O=Google Trust Services LLC,C=US (CA) | CN=GlobalSign Root CA,OU=Root CA,O=GlobalSign nv-sa,C=BE | 15 Nov 2023 | 28 Jan 2028 | ECDSA 384 | SHA256-RSA | 7fe530bf331343bedd821610493d8a1b |
Background: What to check on a remote MCP endpoint →
DNSSEC insecure
Validation of arc-flash-platform.onrender.com. — Not signed
| Zone | DS | Keys | Algorithms | Outcome |
|---|---|---|---|---|
| . | trust_anchor | 20326, 38696 | 8, 8 | Verified |
| com. | present | 19718 | 13 | Verified |
| onrender.com. | absent | Unsigned (proven) parent-signed NSEC/NSEC3 proves an unsigned delegation |
Authentication No authorisation required
The endpoint answered without asking for a token. Anyone who knows the URL can reach it.
| Result | No authorisation required |
|---|---|
| HTTP status | 200 |
Background: How OAuth 2.1 works in the 2026 MCP spec →
Transports 2 probes
| Transport | URL | Outcome | Status | Location |
|---|---|---|---|---|
| streamable-http | https://arc-flash-platform.onrender.com/mcp | Verified | 200 | |
| http (plaintext) | http://arc-flash-platform.onrender.com/mcp | HTTPS enforced | 301 | https://arc-flash-platform.onrender.com/mcp |
The tools this component advertises to a client, with an estimated token cost for each. Expand a tool to see its parameters and schema. The per-tool counts are indicative and are not scored directly; the schema's total context footprint is one signal in Schema Quality & AI Usability. A tool's description is untrusted text the model reads on every call, which is what makes this list a security surface and not just an inventory: how tool poisoning works →
calcular_curto_circuito Curto-circuito (IEC 60909) ~367
Curto-circuito (IEC 60909) pelo motor da plataforma: Icc 3φ/2φ/fase-terra, X/R e pico. Informe a rede por `potencia_curto_mva` OU `icc_rede_kA`. `com_transformador=True` dá o Icc no secundário (trafo_*). `xr_rede`/`xr_trafo` = relações X/R (regem κ, pico ip e assimetria — o making do disjuntor); `tipo_aterramento` ∈ {solido, resistivo, isolado} + `Rn_ohm` regem a corrente de falta fase-terra (Icc_1φ). `com_cabo=True` (+ cabo_secao_mm2/cabo_m) dá o Icc no PONTO de instalação após o cabo (menor que no barramento). Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| Rn_ohm | number | – | – |
| api_key | – | – | – |
| cabo_m | number | – | – |
| cabo_material | string | – | – |
| cabo_num_condutores | integer | – | – |
| cabo_secao_mm2 | number | – | – |
| com_cabo | boolean | – | – |
| com_transformador | boolean | – | – |
| icc_rede_kA | – | – | – |
| potencia_curto_mva | – | – | – |
| tensao_kv | number | yes | – |
| tipo_aterramento | string | – | – |
| trafo_V2_kv | number | – | – |
| trafo_Vcc_pct | number | – | – |
| trafo_kVA | number | – | – |
| xr_rede | number | – | – |
| xr_trafo | – | – | – |
No output schema declared.
No examples provided.
calcular_energia_incidente Energia incidente de arco (IEEE 1584 / NBR 17227) ~371
Energia incidente (Ei, cal/cm²), LAS e categoria de EPI de um arco elétrico, pelo motor IEEE 1584:2018 / ABNT NBR 17227:2025 VALIDADO da plataforma (208 V– 15 kV). `config` ∈ {VCB,VCBB,HCB,VOA,HOA}. Dois patamares de corrente (IEEE 1584:2018 §4.12): `t_arc_s` = tempo de eliminação da proteção na corrente de arco PLENA (Iarc); `t_arc_reduzido_s` = tempo na corrente REDUZIDA (Imin ≈ 0,88·Iarc). Como a corrente reduzida costuma limpar mais devagar (proteção de tempo inverso), o patamar reduzido com frequência GOVERNA o pior caso. Havendo dispositivo com curva inversa, forneça os DOIS tempos; sem `t_arc_reduzido_s`, calcula um único patamar. `larg_mm/alt_mm/prof_mm` = invólucro REAL do equipamento (a correção de tamanho da §4.8 muda o Ei; default = caixa de referência 508³). Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| alt_mm | number | – | – |
| api_key | – | – | – |
| config | string | – | – |
| dist_trabalho_mm | number | yes | – |
| gap_mm | number | yes | – |
| ibf_ka | number | yes | – |
| larg_mm | number | – | – |
| prof_mm | number | – | – |
| t_arc_reduzido_s | – | – | – |
| t_arc_s | number | yes | – |
| tensao_kv | number | yes | – |
No output schema declared.
No examples provided.
calcular_energia_incidente_hv Energia incidente > 15 kV — triagem (OSHA / Lee / EPRI) ~328
Energia incidente para sistemas > 15 kV — FORA do IEEE 1584:2018 / NBR 17227 (arco ao ar livre fase-terra). É TRIAGEM, NÃO laudo: o motor IEEE 1584 da plataforma NÃO é usado; gap e configuração de eletrodos não se aplicam. `metodo` ∈ {osha (padrão), lee, epri}: • osha — OSHA 1910.269 Apêndice E, Tab. 6/7 (base ArcPro). `tipo_trabalho` ∈ {luva (Tab.6, 4–46 kV), vara (Tab.7, 4–800 kV)}. Devolve a BANDA de EPI conservadora (≤4/5/8/12 ou >12 cal/cm²), não um ponto. • lee — cota TEÓRICA superior; exige `dist_trabalho_mm`. • epri — modelo de alta tensão; exige `dist_trabalho_mm` + `comprimento_arco_m` (vão físico fase-terra, em metros). Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| api_key | – | – | – |
| comprimento_arco_m | – | – | – |
| dist_trabalho_mm | – | – | – |
| ibf_ka | number | yes | – |
| metodo | string | yes | – |
| t_ms | number | yes | – |
| tensao_kv | number | yes | – |
| tipo_trabalho | string | – | – |
No output schema declared.
No examples provided.
corrigir_fator_potencia Correção de fator de potência (REN 1.000) ~279
Dimensiona o banco de capacitores para corrigir o fator de potência à meta (REN ANEEL nº 1.000; FP-alvo padrão 0,92). Com `tensao_kV` também dá a corrente nominal do banco e a norma (IEC 60831/60871). `Un_cap_kV` = tensão de placa do capacitor: se ele opera abaixo da Un, entrega MENOS kvar (derating Q∝V²) e a correção real cai — informe p/ não superestimar. `carga_min_pct` = carregamento mínimo (%): dispara o alerta de SOBRECORREÇÃO capacitiva (banco fixo em carga leve → FP capacitivo, faturável). `scc_MVA` = curto na barra do banco → inrush de manobra e a corrente de PROJETO da proteção/cabo do banco (1,5·In BT, IEEE C37.012). Gratuito.
| Name | Type | Req | Description |
|---|---|---|---|
| Un_cap_kV | – | – | – |
| api_key | – | – | – |
| carga_min_pct | – | – | – |
| fp_atual | number | yes | – |
| fp_meta | number | – | – |
| potencia_kW | number | yes | – |
| scc_MVA | – | – | – |
| tensao_kV | – | – | – |
No output schema declared.
No examples provided.
dano_transformador Curva de dano de transformador (IEEE C57.109) ~276
Curva de dano a faltas passantes do transformador (IEEE C57.109/C57.12.59): categoria, corrente de falta passante máxima (In/Z), ponto ANSI e ponto de inrush — para coordenar a proteção a montante. `fases` ∈ {3ph,1ph}; `frequencia_falta` ∈ {infrequent,frequent}; `tipo` ∈ {liquid,dry}; `t_inrush_ms` = patamar de tempo do ponto de inrush. `ligacao` (IEEE C37.91) refere a curva ao OUTRO lado para coordenar com a proteção de lá: {dyg,ygd} Δ-Yg ×0,58 · {dd,yy} ×0,87 · {ygyg,none} ×1,0. Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| Sn_kVA | number | yes | – |
| Vcc_pct | number | yes | – |
| Vn_kV | number | yes | – |
| api_key | – | – | – |
| fases | string | – | – |
| frequencia_falta | string | – | – |
| k_inrush | number | – | – |
| ligacao | string | – | – |
| t_inrush_ms | number | – | – |
| tipo | string | – | – |
No output schema declared.
No examples provided.
dessintonia_capacitor Dessintonia de banco de capacitores (reator anti-ressonância) ~190
Banco dessintonizado (reator série anti-ressonância). Informe `p_pct` (fator de dessintonia XL/XC, ex.: 7 ou 14) OU `L_mH`. Devolve a tensão ELEVADA no capacitor V/(1−p), a corrente pelo reator, o reativo efetivo Q/(1−p), a frequência de sintonia e a classe de tensão sugerida do capacitor (IEC 60831). Com `scc_MVA`, avalia a ressonância paralela com a rede. Gratuito.
| Name | Type | Req | Description |
|---|---|---|---|
| L_mH | – | – | – |
| Q_kvar | number | yes | – |
| Un_cap_kV | – | – | – |
| api_key | – | – | – |
| p_pct | – | – | – |
| scc_MVA | – | – | – |
| tensao_kV | number | yes | – |
No output schema declared.
No examples provided.
dimensionar_cabo Dimensionamento de cabo BT (NBR 5410) ~395
Dimensiona a seção de um cabo BT pela ABNT NBR 5410: ampacidade (Tab. 36-39 + fatores), queda de tensão, coordenação de sobrecarga (§5.3.4.1), neutro e PE. `sistema` ∈ {1FN,2F,3F,3FN}; `metodo` = método de instalação (A1,A2,B1,B2,C,D,E,F,G); `material` ∈ {Cu,Al}; `isolacao` ∈ {PVC,EPR}. `icc_quadro_kA` = Icc presumida no quadro de origem. `n_circuitos_agrupados` = nº de circuitos no mesmo eletroduto/leito (aplica o fator de agrupamento da Tab. 42 — reduz a ampacidade); `arranjo` ∈ {feixe,camada}. `disjuntor_In_A`/`curva_disjuntor` (B,C,D) = o dispositivo REAL instalado (sem eles, assume o menor MCB ≥ Ib, curva C). Gratuito.
| Name | Type | Req | Description |
|---|---|---|---|
| api_key | – | – | – |
| arranjo | string | – | – |
| comprimento_m | number | yes | – |
| curva_disjuntor | string | – | – |
| disjuntor_In_A | – | – | – |
| fp | number | – | – |
| icc_quadro_kA | number | – | – |
| isolacao | string | – | – |
| material | string | – | – |
| metodo | string | – | – |
| n_circuitos_agrupados | integer | – | – |
| potencia_W | number | yes | – |
| queda_max_pct | number | – | – |
| sistema | string | – | – |
| temp_ambiente_C | number | – | – |
| tensao_V | number | yes | – |
No output schema declared.
No examples provided.
dimensionar_tc Dimensionamento de TC (IEC 61869-2) ~361
Dimensiona o TC de proteção (IEC 61869-2 / NBR 6856): menor primário comercial que NÃO satura na falta, considerando o burden REAL (relé+fiação) e o ALF efetivo. `xr` (X/R) = liga o critério de saturação na falta ASSIMÉTRICA (offset CC, IEEE C37.110): um TC que passa no simétrico pode saturar no transitório, atrasar o relé e ELEVAR a energia incidente de arco. `I_load_A`+`Fter` = corrente de carga p/ o critério térmico contínuo. `Ith_A`/`Idyn_A` = corrente térmica (I²t, com `t_curto_s`/`tth_s`) e dinâmica de catálogo → robustez à falta passante (se o TC AGUENTA o curto sem dano térmico/mecânico). `Rct_ohm` = R do secundário de catálogo (None → estimada). Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| ALF | number | yes | – |
| Fter | number | – | – |
| I_load_A | – | – | – |
| Icc_A | number | yes | – |
| Idyn_A | – | – | – |
| Ith_A | – | – | – |
| Rct_ohm | – | – | – |
| api_key | – | – | – |
| burden_VA | number | yes | – |
| cable_ohm | number | yes | – |
| relay_ohm | number | yes | – |
| secundario_A | number | yes | – |
| t_curto_s | number | – | – |
| tth_s | number | – | – |
| xr | – | – | – |
No output schema declared.
No examples provided.
elevacao_temperatura_painel Elevação de temperatura em painel (IEC 60890) ~326
Elevação de temperatura do ar interno de um painel BT (IEC 60890) e verificação de aceitação (61439-1). `perda_W` = perdas dissipadas no invólucro; dimensões em metros. Exposição das faces (muda a área de resfriamento): `face_topo` ∈ {exposto,coberto}; `face_traseira`/`face_laterais` ∈ {exposta,coberta} (coberta = encostada na parede / em fila → aquece mais). `tipo_instalacao` 1–5 (Fig. 4); `limite_equip_C` = limite térmico do equipamento interno (2º veredito); `regime` ∈ {BT, MT (estimativa)}. Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| altura_m | number | yes | – |
| api_key | – | – | – |
| area_ventilacao_cm2 | – | – | – |
| face_laterais | string | – | – |
| face_topo | string | – | – |
| face_traseira | string | – | – |
| largura_m | number | yes | – |
| limite_equip_C | – | – | – |
| n_particoes | integer | – | – |
| perda_W | number | yes | – |
| profundidade_m | number | yes | – |
| regime | string | – | – |
| temp_ambiente_C | number | – | – |
| tipo_instalacao | integer | – | – |
| ventilado | boolean | – | – |
No output schema declared.
No examples provided.
gerar_memorial Memorial de cálculo (laudo na plataforma) ~63
Memorial assinável + etiqueta ANSI/NBR. NUNCA é emitido autonomamente por IA — o documento é preparado na sua conta da plataforma para revisão e assinatura do responsável técnico.
| Name | Type | Req | Description |
|---|---|---|---|
| api_key | – | – | – |
| referencia_calculo | string | yes | – |
No output schema declared.
No examples provided.
grupo_gerador Grupo gerador — degrau de carga (ISO 8528) ~314
Afundamento transitório de tensão ao aplicar um degrau de carga a um grupo gerador (ISO 8528-5, etapa 1: tensão), via reatância transitória X'd. `modo` ∈ {bloco (degrau_kVA+degrau_fp), motor (motor_kW, partida DOL)}. `XR` = X/R da X'd (ângulo da queda). `cabo_mm2`+`cabo_m` = alimentador gerador→carga (a queda no cabo soma no ΔV). `dv_limite_pct` sobrepõe o limite da classe — OBRIGATÓRIO para `classe_iso="G4"` (limite por acordo). `motor_fp_rotor_bloqueado` = FP de partida (modo motor). Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| Sn_kVA | number | yes | – |
| XR | number | – | – |
| api_key | – | – | – |
| cabo_m | number | – | – |
| cabo_mm2 | – | – | – |
| classe_iso | string | – | – |
| degrau_fp | number | – | – |
| degrau_kVA | – | – | – |
| dv_limite_pct | – | – | – |
| modo | string | – | – |
| motor_Ip_In | number | – | – |
| motor_fp_rotor_bloqueado | number | – | – |
| motor_kW | – | – | – |
| tensao_V | number | yes | – |
| xd_pct | number | – | – |
No output schema declared.
No examples provided.
k_factor_transformador K-factor de transformador (UL 1561) ~123
K-factor (UL 1561) a partir do espectro de corrente {ordem: % de I1}, ex.: {"3": 70, "5": 45, "7": 30}. Devolve o K-factor, o K-rating comercial (trafo K-rated para cargas não-lineares), o F_HL (derating de perdas parasitas, IEEE C57.110) e o THD de corrente. Gratuito.
| Name | Type | Req | Description |
|---|---|---|---|
| api_key | – | – | – |
| espectro_harmonico | object | yes | – |
No output schema declared.
No examples provided.
listar_dispositivos Catálogo de dispositivos de proteção ~111
Lista o catálogo de dispositivos (devices_db) para descobrir o `device_id` usado no modo catálogo de tempo_de_atuacao. Por padrão só MCCB/ACB (trip eletrônico com In_A real); `tipo` filtra ('MCCB','ACB','Relay','MCB','Fuse','Transformer'); `todos=True` inclui todos os tipos. Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| api_key | – | – | – |
| tipo | – | – | – |
| todos | boolean | – | – |
No output schema declared.
No examples provided.
listar_ferramentas Catálogo de ferramentas ~29
Lista a prateleira de cálculos de engenharia elétrica e o tier de cada um.
Input schema present but exposes no named parameters.
No output schema declared.
No examples provided.
montar_rede Montar rede multibarra e calcular Icc em todas as barras (IEC 60909) ~954
Monta uma REDE MULTIBARRA (concessionária → transformadores → cabos → quadros) e calcula o curto-circuito IEC 60909 em TODAS as barras de uma vez, pelo mesmo motor validado da plataforma (redução nodal do Anexo B: aceita alimentação radial, em paralelo e malha). Use quando o usuário tem os dados de VÁRIOS equipamentos — típico de quem acabou de ler um datasheet, uma carta da concessionária ou um memorial antigo — em vez de chamar `calcular_curto_circuito` (que é de UM ponto) várias vezes. Devolve também `projeto_json`: o arquivo de projeto da plataforma com a rede inteira. Entregue esse conteúdo ao usuário para salvar como `.json` e abrir em "Abrir projeto" no app — a rede aparece nas tabelas para ele CONFERIR e seguir para coordenograma, arco elétrico e memorial. Nenhum valor extraído de documento deve virar laudo sem essa conferência humana. ── barras: lista de objetos ──────────────────────────────────────────────── {"id": "SE_BT", "label": "Subestação 480 V", "Vn_kV": 0.48} `id` é o identificador único (sem espaços é mais seguro); `Vn_kV` é a tensão NOMINAL da barra em kV (0,48 = 480 V). A barra de conexão com a concessionária é a que NÃO recebe nenhum elemento (nenhum `to_id` aponta para ela) — é ela a raiz da rede. ── elementos: lista de objetos (o que liga uma barra à outra) ────────────── element_type "transformer": {"from_id","to_id","element_type":"transformer", "Sn_kVA":1000,"Vcc_pct":5.0,"Pcu_W":10000,"XR_trafo":null} Sn e Vcc são de PLAQUETA e obrigatórios (>0). `Pcu_W` = perdas no cobre; `XR_trafo` (opcional) sobrepõe o X/R estimado por Pcu. element_type "cable" (ou "busbar"): {"from_id","to_id","element_type":"cable", "secao_mm2":95,"material":"Cu","comprimento_m":40,"num_conductors":1} Liga barras de MESMA tensão (para mudar de tensão use "transformer"). element_type "reactor": {"from_id","to_id","element_type":"reactor", "u_kR_pct":6,"I_rR_A":400} (reator limitador, §6.5 — u_kR e I_rR de plaqueta) ── fo…
| Name | Type | Req | Description |
|---|---|---|---|
| api_key | – | – | – |
| barras | array | yes | – |
| elementos | array | yes | – |
| fonte | object | yes | – |
| lang | string | – | – |
| motores | – | – | – |
No output schema declared.
No examples provided.
partida_motor Partida de motor — afundamento de tensão ~440
Afundamento de tensão na partida de motor por divisor fasorial fonte→cabo→motor (C ∝ V²). `fonte_tipo` ∈ {scc (nível de curto `scc_MVA`), trafo (`fonte_trafo_kVA`+`fonte_trafo_Vcc_pct`, com rede a montante opcional `fonte_scc_montante_MVA`), gerador (`fonte_gmg_kVA`+`fonte_gmg_xd_pct`, X'd transitório)} — trafo dedicado e GMG são os casos SEVEROS de afundamento. `metodo` ∈ {direta, estrela_triangulo, compensadora_65, compensadora_80, soft_starter, vfd} (aceita 'compensadora'→tap 80% e 'soft'→soft_starter). `fp_partida` = FP de rotor bloqueado; `Cp_Cn` = conjugado de partida/nominal; `C_load_pu` = conjugado da carga (×Cn) — SEM ele a aceleração NÃO é avaliada. Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| C_load_pu | – | – | – |
| Cp_Cn | number | – | – |
| In_A | – | – | – |
| Ip_In | number | – | – |
| api_key | – | – | – |
| cabo_m | number | – | – |
| cabo_mm2 | – | – | – |
| dv_limite_pct | number | – | – |
| eta | number | – | – |
| fonte_gmg_kVA | – | – | – |
| fonte_gmg_xd_pct | number | – | – |
| fonte_scc_montante_MVA | – | – | – |
| fonte_tipo | string | – | – |
| fonte_trafo_Vcc_pct | number | – | – |
| fonte_trafo_kVA | – | – | – |
| fp | number | – | – |
| fp_partida | number | – | – |
| metodo | string | – | – |
| potencia_kW | number | yes | – |
| scc_MVA | – | – | – |
| tensao_V | number | yes | – |
No output schema declared.
No examples provided.
puxamento_cabo Puxamento de cabo (IEEE 1185/525) ~347
Tração de puxamento de cabo (IEEE 1185/525): tração no cabrestante, SWBP (pressão lateral nas curvas), ocupação do duto (NBR 5410) e tração máxima admissível. `n_cabos` ∈ {1,3} (trifólio). `curvas_graus` = lista dos ângulos das curvas/cotovelos (graus) — SEM curvas a SWBP (que costuma GOVERNAR) sai zero; `curva_raio_m` = raio das curvas (m). `attachment` ∈ {olhal (no condutor), malha (na capa, teto 500 kgf)}. `convencao` ∈ {BR,NA,EU}; `swbp_classe`/`cabo_classe` ∈ {BT, MT, controle, armado, ...}. Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| api_key | – | – | – |
| attachment | string | – | – |
| cabo_classe | string | – | – |
| comprimento_m | number | yes | – |
| convencao | string | – | – |
| curva_raio_m | number | – | – |
| curvas_graus | – | – | – |
| duto_D_mm | number | yes | – |
| incl_graus | number | – | – |
| material | string | yes | – |
| mu | number | – | – |
| n_cabos | integer | – | – |
| od_mm | number | yes | – |
| peso_kg_m | number | yes | – |
| secao_mm2 | number | yes | – |
| swbp_classe | string | – | – |
No output schema declared.
No examples provided.
solicitar_orcamento Solicitar orçamento de estudo/laudo (ART) ~145
Encaminha um pedido de ORÇAMENTO de estudo/laudo assinável com ART (arc flash, curto-circuito, seletividade, adequação NR-10) direto do chat. Informe o e-mail de contato e o escopo (ex.: nº de painéis, classe de tensão, prazo, cidade). A equipe responde pelo e-mail informado. Não consome o limite das calculadoras — funciona inclusive quando o uso gratuito do dia esgotou.
| Name | Type | Req | Description |
|---|---|---|---|
| api_key | – | – | – |
| string | yes | – | |
| empresa | string | – | – |
| escopo | string | – | – |
| nome | string | – | – |
No output schema declared.
No examples provided.
tempo_de_atuacao Tempo de atuação da proteção (IEC 60255-151 / IEEE C37.112) ~351
Tempo de atuação de um dispositivo de proteção à corrente de falta, pela curva composta 4-segmentos do motor da plataforma (IEC 60255-151 / IEEE C37.112): 51 inversa · 50 curto-tempo · 50 instantânea. É o ELO entre o curto e o arco: encadeie calcular_curto_circuito → tempo_de_atuacao → calcular_energia_incidente (o `tempo_s` daqui é o `t_arc_s`, o parâmetro mais difícil de estimar à mão). MANUAL (universal): `pickup_A` = pickup do 51 (relé: RTC×tap; disjuntor: Ir); `curva` ∈ IEC/IEEE; `tms` = TMS (IEC) ou time-dial (IEEE); `instantaneo_A`+`t_disjuntor_ms` (50 instantânea) e `curto_tempo_A`+`t_curto_tempo_ms` (50 temporizada) são opcionais — sem eles, só a inversa opera. CATÁLOGO: `device_id` de MCCB/ACB (use listar_dispositivos). Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| api_key | – | – | – |
| corrente_falta_A | number | yes | – |
| curto_tempo_A | – | – | – |
| curva | string | – | – |
| device_id | – | – | – |
| instantaneo_A | – | – | – |
| pickup_A | – | – | – |
| t_curto_tempo_ms | number | – | – |
| t_disjuntor_ms | number | – | – |
| tms | number | – | – |
No output schema declared.
No examples provided.
tempo_partida_motor Tempo de partida de motor (curva T×n + rotor térmico) ~353
Simula a partida DIRETA no tempo (RK4, J·dω/dt = T_motor − T_carga): tempo de aceleração, se o motor PARTE ou trava, e o térmico de rotor bloqueado (I²t da partida vs tempo de rotor bloqueado de placa, critério Petrobras N-313). `polos` = nº de polos; `inercia_kgm2` = J total (motor+carga); `tipo_carga` ∈ {constante, linear, parabolica (bomba/ventilador)}; `conjugado_partida_carga_pu` /`conjugado_pleno_pu` = conjugado da carga (×Cn do motor) em n=0 e a plena rotação; `t_rotor_bloqueado_s` liga o veredito térmico. Gratuito.
| Name | Type | Req | Description |
|---|---|---|---|
| Cp_Cn | number | – | – |
| Ip_In | number | – | – |
| api_key | – | – | – |
| cabo_m | number | – | – |
| cabo_mm2 | – | – | – |
| conjugado_partida_carga_pu | number | – | – |
| conjugado_pleno_pu | number | – | – |
| eta | number | – | – |
| fp | number | – | – |
| fp_partida | number | – | – |
| inercia_kgm2 | number | yes | – |
| polos | integer | yes | – |
| potencia_kW | number | yes | – |
| scc_MVA | number | yes | – |
| t_rotor_bloqueado_s | – | – | – |
| tensao_V | number | yes | – |
| tipo_carga | string | – | – |
No output schema declared.
No examples provided.
verificar_seccionamento Seccionamento automático (NBR 5410) ~390
Verifica a proteção contra choque por seccionamento automático (ABNT NBR 5410:2004 §5.1.2.2). TN: Zs ≤ U0/Ia (informe Ia OU disjuntor In+curva_mcb). TT: RA ≤ 50/IΔn (informe i_dn_mA + RA). `situacao` = 1 (seco/usual, U_L=50 V) ou 2 (molhado/externo, U_L=25 V e tempo da Tab. 25 mais rígido). `R_montante_ohm`+`X_montante_ohm` = impedância do laço A MONTANTE (fonte/trafo + alimentadores) — sem ela o Zs conta só o circuito e o veredito fica OTIMISTA. `circuito_tipo` ∈ {terminal_le32, distribuicao_gt32}; `secao_pe_mm2` = PE real (None → mínimo da Tab. 58). Gratuito (uso limitado).
| Name | Type | Req | Description |
|---|---|---|---|
| Ia_A | – | – | – |
| RA_ohm | – | – | – |
| R_montante_ohm | number | – | – |
| T_op | number | – | – |
| U0_V | number | yes | – |
| X_montante_ohm | number | – | – |
| api_key | – | – | – |
| circuito_tipo | string | – | – |
| comprimento_m | number | – | – |
| curva_mcb | – | – | – |
| disjuntor_In_A | – | – | – |
| i_dn_mA | – | – | – |
| material | string | – | – |
| secao_fase_mm2 | number | – | – |
| secao_pe_mm2 | – | – | – |
| sistema | string | – | – |
| situacao | integer | – | – |
No output schema declared.
No examples provided.
What is the Arc Flash Platform — Estudos Elétricos MCP server?
Arc Flash Platform — Estudos Elétricos is an MCP server listed in the public MCP registry as io.github.alessandropeng/arc-flash-platform. Cálculos de engenharia elétrica pela norma brasileira (NBR), validados, com citação normativa. This page covers its hosted endpoint (https://arc-flash-platform.onrender.com/mcp).
Is the Arc Flash Platform — Estudos Elétricos MCP server safe to use?
Arc Flash Platform — Estudos Elétricos scores 79 out of 100 on VerifyMCP. That is a record of what we were able to check automatically, not an endorsement. The category breakdown on this page shows every signal behind the number, including the ones we could not confirm.
What tools does the Arc Flash Platform — Estudos Elétricos MCP server expose?
Arc Flash Platform — Estudos Elétricos exposes 21 tools: listar_ferramentas, calcular_energia_incidente, calcular_energia_incidente_hv, calcular_curto_circuito, montar_rede, and 16 more. Their descriptions and schemas cost roughly 6,513 tokens of context every time the server is loaded.
Does the Arc Flash Platform — Estudos Elétricos MCP server require authentication?
No. We connected to Arc Flash Platform — Estudos Elétricos without credentials and it answered, so anything it exposes is reachable by anyone who knows the address.
Is the Arc Flash Platform — Estudos Elétricos MCP server still maintained?
Arc Flash Platform — Estudos Elétricos is still listed as active in the MCP registry. We last reached this channel on 3 October 2026. Those dates come from our own scans of the registry and the channel itself, not from anything the publisher announced.